1 / 5
Model No. : | VV |
---|---|
Brand Name : | HUAYUAN YONGTONG |
Type : | Insulated |
Beijing, Beijing, China
Description du produit
1. NORMES APPLICALBE
Le câble offert par Beijing Huayuan doit être conçu, fabriqué et testé conformément aux normes internationales suivantes:
Quality Control Standard |
|
ISO 9001 |
Quality Management Systems |
ISO 14001 |
Environmental Management Systems |
Component Material Standard |
|
IEC 60228 |
Conductors of insulated cables |
Reference Standard |
|
IEC 60502.1 |
Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV) |
IEC 60227.5 |
Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V –part 5 :Flexible cables(cords) |
2.CABLES STRUCTURE
CU / PVC / PVC 0,6 / 1 kV 1 × 150 mm2
Construction |
Nominal Thickness(mm) |
Nominal Diameter(mm) |
1 Stranded non-compacted circular copper conductor(soft class 5) |
/ |
16.96 |
2 Wrapping tape |
0.2 |
17.6 |
3 PVC insulation |
1.8 |
21.2 |
4PVC outer sheath |
1.6 |
24.2 |
3.Caractéristiques techniques garanties
No |
DESCRIPTION |
UNIT |
VALUEREQUIRED |
1 |
Manufacturer |
|
Beijing Huayuan Gaoke Cable Co.,Ltd. |
2 |
Cable size |
mm2 |
150 |
3 |
Cable type |
|
CU/PVC |
4 |
Voltage Grade |
kV |
0.6/1(1.2) |
5 |
Reference Standard |
|
IEC 60502.1 IEC60227 |
6 |
No. and cross sectional area of conductor |
|
1×150mm2 |
7 |
Conductor material |
|
Copper |
8 |
Shape |
|
stranded non-compacted circular (soft class 5) |
9 |
Nominal diameter of conductor |
mm |
4.0 |
10 |
Insulation material |
|
Soft PVC |
|
Colour |
|
Black |
11 |
Nominal thickness of insulation |
mm |
1.8 |
12 |
Nominal diameter over insulation |
mm |
21.2 |
13 |
Inner sheath material |
|
NA |
14 |
Nominal thickness of inner sheath |
mm |
NA |
15 |
Outer sheath material |
|
Soft PVC |
|
Colour |
|
Black |
16 |
Nominal thickness of outer sheath |
mm |
1.6 |
17 |
Nominal overall diameter of cable |
mm |
24.4 |
18 |
Short circuit current rating(t=1.0sec) |
|
|
|
Of conductor |
kA |
17.5(max) |
19 |
Max. conductor temperature in short circuit |
℃ |
160(not exceed 5s) |
20 |
Approx. weight of cable |
kg/km |
1520 |
21 |
Minimum bending radius |
mm |
90 |
22 |
Max. D.C. Conductor resistance at 20`C |
Ω/km |
0.129 |
23 |
Max. conductor temperature on continuous |
℃ |
70 |
24 |
Max. current rating in air |
A |
325( temperature 40° C ) |
25 |
Max. current rating in underground |
A |
285(depth of laying 700 mm ,thermal resistivity of soil 1.0 k.m/W,temperature 25℃) |
Compagnie
Atelier
Paquet
Livraison et paiement
Honneur
Notre client
1.0.6Kv Câble 2.750v Câble 3.Three Core En Aluminium Conducteur 4. Câble De Contrôle Isolé 5.Pvc Câble De Contrôle Flexible 6. Câble De Câble Encrassé
Beijing, Beijing, China
Envoyez votre demande à ce fournisseur