1 / 4
Model No. : | NYCY |
---|---|
Brand Name : | HUAYUAN YONGTONG |
Brand : | HUAYUAN YONGTONG |
Beijing, Beijing, China
Description du produit
Le câble offert par Beijing Huanyuan doit être conçu, fabriqué et testé conformément aux normes internationales suivantes:
Quality Control Standard |
|
ISO 9001 |
Quality Management Systems |
ISO 14001 |
Environmental Management Systems |
Component Material Standard |
|
IEC 60228 |
Conductors of insulated cables |
Cable Standard |
|
IEC 60502-1 |
Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV) |
2.CABLES STRUCTURE
CU / PVC / PVC / CWS / PVC 0,6 / 1 kV 3 × 10/10 mm2
Construction |
Nominal thickness(mm) |
Nominal Diameter(mm) |
1 Solid core round copper conductor |
/ |
3.35 |
1.0 |
5.6 |
|
3 Laying up |
PP filling |
12.0 |
4 Warping tape |
0.2 |
12.6 |
5 PVC Inner sheath |
1.0 |
14.6 |
6 Copper wire screen |
cross-sectional area10mm2(nominal) |
16.6 |
7 Warping tape |
0.2 |
17.2 |
8UV-resistant Black PVC outer sheath |
1.8 |
20.8 |
3.Caractéristiques techniques garanties
Concentric PVC cable NYCY 3 x 10 RE/10 mm² Cable |
|||
No |
DESCRIPTION |
UNIT |
VALUEREQUIRED |
|
Manufacturer |
|
Beijing Huayuan Gaoke Cable Co.,Ltd. China |
1 |
Cable size |
mm2 |
3 x 10 RE/10 mm² |
2 |
Cable type |
|
Concentric PVC cable NYCY |
3 |
Voltage Grade(Uo/U(Um) |
KV |
0.6/1 (1.2) |
4 |
Reference Standard |
|
IEC 60502-1 |
5 |
No. and cross sectional area of conductor |
|
3×10 mm2 |
6 |
Conductor material |
|
Solid Copper |
7 |
Shape |
|
Round |
9 |
Nominal diameter of conductor |
mm |
3.55 |
10 |
Material of insulation |
|
|
12 |
Nominal thickness of insulation |
mm |
1.0 |
13 |
Nominal diameter over insulation |
mm |
5.6 |
14 |
Outer sheath material |
|
PVC Black (UV-resistant) |
15 |
Nominal thickness of outer sheath |
mm |
1.8 |
16 |
Minimum thickness of outer sheath |
mm |
1.2 |
17 |
Nominal overall diameter of cable |
mm |
20.8 |
18 |
Short circuit current rating(t=1.0sec) |
|
|
|
Of conductor |
kA |
1.2 |
|
Of screen |
kA |
1.2 |
19 |
Approx. weight of cable |
kg/km |
620 |
20 |
Minimum bending radius |
mm |
312 |
21 |
Max.DC. Conductor resistance at20`C |
Ω/km |
1.83 |
22 |
Max.DC. Screen resistance at20`C |
Ω/km |
1.83 |
23 |
Max. current rating in air(40° C , 1 circuit touch ) |
A |
65 |
24 |
Max. current rating in ground (depth of laying 1200 mm ,thermal resistivity of soil 1.2 k.m/W,1 circuit touch, temperature 25℃) |
A |
50 |
25 |
Max. conductor temperature on continuous |
℃ |
70 |
26 |
Max. conductor temperature in short circuit |
℃ |
160(not exceed 5s) |
4. Exigences de test pour les câbles d'alimentation BT
L'essai du câble doit être effectué conformément à la norme applicable des câbles d'alimentation de 0,6 / 1 kV. Les éléments d'essai suivants doivent être réalisés conformément aux normes CEI pertinentes.
No. |
Test item |
Routine tests |
|
1 |
measurement of the electrical resistance of conductors |
2 |
Voltage test |
Sample tests |
|
1 |
conductor examination |
2 |
check of dimensions |
5. CONDITIONS D'EMBALLAGE POUR Câbles d'alimentation 0,6 / 1kV
Les câbles doivent être enroulés sur des tambours en acier. Le marquage indélébile doit être imprimé sur la surface de la bride du tambour conformément aux exigences du client.
Cable Type |
Drum length(m) |
Drum Dimensions (mm) |
|||
|
|
D |
d |
L2 |
L1 |
CU/PVC/PVC/CWS/PVC 0.6/1 kV 3×10/10 mm2 |
500 |
1000 |
570 |
700 |
850 |
Usine et équipement
P ackage
Livraison et paiement
Honneur
Beijing, Beijing, China
Envoyez votre demande à ce fournisseur